Gauge indication | Refrigerant cycle | Probable cause | Corrective action |
Both high- and low-pressure sides are too high. | The pressure returns to normal soon after sprinkling water on condenser. | Overfilled refrigerant. | Collect all refrigerant, evacuate refrigerant cycle again, and then refill it with the specified amount of refrigerant. |
Air flow to condenser is insufficient. | Insufficient condenser cooling performance.
|
| |
When A/C compressor is stopped, a high-pressure reading quickly drops by approximately 196 kPa (1.96 bar, 2 kg/cm2, 28 psi). It then gradually decreases. | Air mixed in refrigerant cycle. | Collect all refrigerant, evacuate refrigerant cycle again, and then refill it with the specified amount of refrigerant. | |
| Expansion valve opened too much (excessive flow of refrigerant). | Replace expansion valve. | |
High-pressure side is excessively high and low-pressure side is too low. | High-pressure pipe and upper side of condenser become hot, however, liquid tank does not become so hot. | Clogged or crushed high-pressure pipe located between compressor and condenser. | Repair or replace the malfunctioning parts. |
High-pressure side is too low and low-pressure side is too high. |
| Malfunction in A/C compressor system (insufficient A/C compressor pressure operation).
| Replace A/C compressor. |
Both high- and low-pressure sides are too low. |
| Clogged expansion valve.
| Eliminate foreign material from expansion valve, or replace it. |
| Malfunction in inner liquid tank (clogged strainer). | Replace condenser & liquid tank. | |
Evaporator becomes frosted. | Clogged or crushed low-pressure pipe. | Repair or replace malfunctioning parts. | |
Malfunction in fin thermo sensor. | Check fin thermo sensor system. Refer to Diagnosis Procedure: B24A4-11 . | ||
There is a small temperature difference between the high and low pressure pipes for refrigerant cycle. |
|
| |
Low-pressure side sometimes becomes negative. |
|
|
|
Hunting in high-pressure side. | There is no temperature difference between high- and low-pressure sides. | Malfunctioning variable valve in A/C compressor. | Replace A/C compressor. |